DS-E Series1~6KVAUser’s Manual
14
1Place UPS on flat floor (avoid oblique and ragged floor).
2Keep good ventilation, the distance of the back and side to the wall should
be above 30cm~50cm, to facilitate heat emission.
3Avoid placing it in the location with sunniness, rain and dampness.
4Never place it in the location with corrosive air.
5Do not place articles on or around the UPS, to prevent the vent hole from
being blocked. No person is allowed to sit on it.
3.4 Selection of Cable
3.4.1 Selection of Input Air Switch
Before the input coil in of the equipment, install an air switch or a distribution
box compliant with the power and capability of the equipment, to isolate it with
commercial power. Consider especially the charge power and the current
shock, the input air switch can be higher than 1.5-2 times most current of UPS
input, which is without creepage protection in order to avoid error action. The
distribution box should be better to be manufactured by professional company.
Please refer to Table 3-1.
Table 3-1 Recommended Sectional input air switch
DS1000E DS2000E DS3000E DS6000E
Most
Current
A
Recommended
Air switch
A
Most
Current
A
Recommended
Air switch
A
Most
Current
A
Recommended
Air switch
A
Most
Current
A
Recommended
Air switch
A
AC
Input
6 10 12 20 18 32 36 50
DC
Input
26 50 20 32 30 50 50 100