䊳
Set/read orifice rim heater mode (OTT Pluvio
2
S with orifice rim heater)
aOCHb! ab<CR><LF> Set mode
aOCH! ab<CR><LF> Read mode
a – sensor address
b – 0 = Orifice rim heater disabled
1 = Mode #1; continuously ON
2
= Mode #2; temperature range control
3 = Modus 3; NWS Standard
4 = Modus 4; precipitation events
䊳
Set/read orifice rim heater target temperature (OTT Pluvio
2
S with orifice rim heater)
aOCHSpb! apb<CR><LF> Set target temperature
aOCHS! apb<CR><LF> Read target temperature
a – sensor address
p – sign (+)
b – 2 … 9 (+2 … +9 °C);
factory setting +4 °C
䊳
Set/read orifice rim heater lower temperature limit (OTT Pluvio
2
S with orifice rim heater)
Orifice rim heater mode: #2
aOCHGpbb! apbb<CR><LF> Set lower temperature limit
aOCHG! apbb<CR><LF> Read lower temperature limit
a – sensor address
p – sign (+,–)
bb – 40 … 9 (–40 … +9 °C);
factory setting –30 °C
䊳
Set/read orifice rim heater on-time/after-run time (OTT Pluvio
2
S with orifice rim heater)
Orifice rim heater mode: #3, #4
aOCHDbbbb! abbbb<CR><LF> Set on-time/after-run time
aOCHD! abbbb<CR><LF> Read on-time/after-run time
a – sensor address
bbbb – 1 … 1440 (1 … 1440 minutes);
factory setting 20 minutes
䊳
Set/read orifice rim heater starting time (OTT Pluvio
2
S with orifice rim heater)
Orifice rim heater mode: #3
aOCHZhh:mm:ss! ahh:mm:ss<CR><LF> Set starting time
aOCHZ! ahh:mm:ss<CR><LF> Read starting time
a – sensor address
hh:mm:ss – 00:00:00 … 23:59:59;
factory setting 14:00:00 Uhr
䊳
Set/read orifice rim heater self-test interval (OTT Pluvio
2
S with orifice rim heater)
Orifice rim heater mode: #1, #2, #3, #4
aOCHTbbbb! abbbb<CR><LF> Set self-test interval
aOCHT! abbbb<CR><LF> Read self-test interval
a – sensor address
bbbb – 1 … 10 080 (1 … 10 080 minutes);
factory setting 60 minutes*
* by OTT Pluvio
2
operating software adjustable values: 1, 12, 24 hours; 2, 3, 4, 5, 6, 7 days
33