38
X
Function Parameter List
█
Monitor Parameter List
No Monitor item Unit Display
n001 Output Frequency Hz
Displays output frequency of inverter (in
increments of 0.1Hz).
n002 Output Current A
Displays output current of inverter (in
increments of 0.1A).
n003 Output Voltage V AC
Displays output voltage of inverter (in
increments of 1V AC).
n004 Internal DC Voltage V DC
Displays the internal DC voltage of
inverter (in increments of 1V DC).
n005 Set Frequency Hz
Displays the set frequency (in increments
of 0.1Hz).
n006 Communication Station No. -
Displays the current set communication
station No.
n007 Operation Times of Timer Times
Displays continuous operation times of
timer in one cycle.
n008 Alarm Type - Displays the content of alarm LED.
n009 Input Signal Status - Displays contact data.
n010 Output Signal Status - Displays contact data.
n011 PID Set Value (SP) %
Displays the set value during PID control
(SP).
n012 PID Target Value (PV) %
Displays the target value during PID
control (PV).
n013 PID Output Value (MV) %
Displays the output value during PID
control (MV).
n014 Accumulative Operation Time -
Displays the accumulative operation time
of inverter.
n015
Accumulative Operation Time of
Fan
-
Displays the accumulative operation time
of inverter fan.
n016 Abnormality Display (Latest) - Displays abnormalities.
n017
Abnormality Display (Second to
latest)
- Displays abnormalities.
n018
Abnormality Display (Third to
latest)
- Displays abnormalities.
n019
Abnormality Display (Fourth to
latest)
- Displays abnormalities.
n020 Unit Program Version - 1.00 to 99.99
n021 Detected Value of Pulse Input Hz
Displays the frequency value detected
according to the pulse input signal.
n022 Winding Length m Displays the current winding length.
n023 For Manufacturer Confirmation - -
n024 For Manufacturer Confirmation - -
n025 Analog Input 1 %
Displays the analog input terminal No.12
corresponding percentage
n026 Analog Input 2 %
Displays the analog input terminal No.14
corresponding percentage
n027 Internal Module Temperature ℃ Displays the internal module temperature.