50
No. Function name
Changes
during RUN
Setting range Unit
Initial
value
P127
Detection
Frequency
(Output TR)
○ 0.0, 0.2 to 400.0 0.1[Hz] 0.2
P128
Detection
Frequency
(Output RY)
○ 0.0, 0.2 to 400.0 0.1[Hz] 0.2
P129
Current Detection
Level
○ 0.1 to 100.0 0.1[A] *4
P130
Current Detection
Delay Time
○ 0.1 to 10.0 0.1[sec] 0.1
P131
RS485
Communication
Protocol*6
○
0 :MEWTOCOL
1 :Modbus - RTU
2 :Modbus - ASCII
- 0
P132
RS485
Communication
Station No.*6
○ 01 to 31 - 01
P133
RS485
Communication
Speed*6
○
48 :4800
96 :9600
192 :19200
384 :38400
576 :57600
1152 :115200
bps 1152
P134
RS485 Stop Bit
Length*6
○
1 :1bit
2 :2bit
bit 1
P135
RS485 Parity
Check*6
○
0: Without parity check
1: Odd parity
2: Even parity
- 0
P136
RS485 Timeout
Detection*6
○ 0.0 · 0.1 to 60.0 0.1[sec] 0.0
P137
Waiting Time
for RS485
Transmission *6
○ 1 to 1000 1[msec] 1
P138
Judging Time
for RS485 TEXT
Completion *6
○ 3 to 200 1[msec] 3
P139
2nd Base
Frequency
45.0 to 400.0 0.1[Hz] 50.0
P140 2nd Torque Boost*7 ○
0 to 40: Manual torque boost
Auto: Automatic torque boost
1[%] *4
P141
2nd Electronic
Thermal Selection
○
0: OL trip occurs with current up to
140% of its rating for 1 minute.
1: Without output frequency derating
2: With output frequency derating
3: Forced air-cooled motor specification
- 2
P142
2nd Thermal
Current Setting
○ 0.1 to 100.0 0.1[A] *4
P143
2nd Change Point
Frequency 1
○ 0.2 to 400.0 0.1[Hz] 0.2
P144
2nd Change Point
Voltage 1
○ 0.0 to 100.0 0.1[%] 0.0