12.3 Automatic Operation
Automatic operation can be set using remote control.
This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature.
After judged the temperature, the operation mode is determined by referring to the below standard.
Intake Air
Temperature
23°C
Cooling Operation
Soft Dry Operation
Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the
setting temperature as shown in table below.
Setting Temperature (Standard)
Cooling Operation 25°C
Soft Dry Operation 22°C
The setting temperature for all the operations can be changed one level up or one level down from the standard
temperature as shown in below table by pressing on the temperature up or temperature down button at remote
control.
Cooling Soft Dry
Higher +2°C
27°C 24°C
Standard ±0°C
25°C 22°C
Lower -2°C
23°C 20°C
The operation mode judging temperature and standard setting temperature can be increased by 2°C
permanently, by open the circuit of JX03 at indoor units printed circuit board.
Intake Air
Temperature
23°C
Cooling Operation
Soft Dry Operation
Setting Temperature (Standard)
Cooling Operation 27°C
Soft Dry Operation 24°C