14.1.5 Automatic Operation
This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode and indoor intake air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the
indoor intake air temperature.
Every 10 minutes, the indoor temperature is judged.
For the 1st judgment
o If indoor intake temperature - remote control setting temperature ≥ 2.0°C, COOL mode is decided.
o If -2.0°C ≤ indoor intake temperature - remote control setting temperature < 2.0°C, DRY mode is decided.
o If indoor intake temperature - remote control setting temperature < -2.0°C, HEAT mode is decided.
For the 2nd judgment onwards
o If indoor intake temperature - remote control setting temperature ≥ 3.0°C, if previous operate in DRY mode,
then continue in DRY mode, otherwise COOL mode is decided.
o If -2.0°C ≤ indoor intake temperature - remote control setting temperature < 3.0°C, maintain with previous
mode.
o If indoor intake temperature - remote control setting temperature < -2.0°C, HEAT mode is decided.
14.2 Indoor Fan Motor Operation
14.2.1 Basic Rotation Speed (rpm)
A. Basic Rotation Speed (rpm)
i. Manual Fan Speed
[Cooling, Dry]
Fan motor’s number of rotation is determined according to remote control setting.
Remote control ○ ○ ○ ○ ○
Tab Hi Me+ Me Me- Lo
When thermostat off, the fan speed will be limited to max Me fan.
The indoor fan will resume running according to the set fan speed when thermostat on.
[Heating]
Fan motor’s number of rotation is determined according to remote control setting.
Remote control ○ ○ ○ ○ ○
Tab SHi Me+ Me Me- Lo
6.05.04.03.02.01.00.0-1.0-2.0-3.0-4.0-5.0-6.0
Dry Cool
Heat
6.05.04.03.02.01.00.0-1.0-2.0-3.0
-4.0
-5.0-6.0
Maintain
current mode
Cool
/Dry
Heat