Mini VRF SYSTEM
Remote Controller Functions
5 - 17
2. Detailed Settings Function
5
Item code Item Description
10 Unit type
Set when the indoor unit EEPROM memory is replaced during servicing.
11 Indoor unit capacity
12
System (outdoor unit)
address
These are not set at the time of shipping from the factory.
These must be set after installation if auto address setting is not performed.
13 Indoor unit address
14 Group address
17
Cooling intake temperature
shift
Shifts the intake temperature during cooling and dry operation.
(Enabled only when the body thermostat is used.)
Increase this value when it is difficult to turn the thermostat ON.
18
Automatic stop time after
operation start
The time at which an indoor unit is automatically stopped after operation starts
can be set in increments of 5 minutes.
1E
Temperature shift for
cooling/heating change in
“auto heat/cool” mode
“Auto heat/cool” selects the operating mode automatically based on the
difference between the room temperature and the temperature set on the
remote controller. This setting establishes a shift temperature for the heating/
cooling temperature setting relative to the remote controller temperature
setting.
Cooling temperature setting
Remote controller temperature setting
Heating temperature setting
Shift temperature
(+)
Shift temperature
(–)
Item code Item
Setting data
No. Description
0000
0001
0002
0003
0000
Refrigerant leak sensor
life notification and
refrigerant leak alarm
reset
Operation setting for
nanoe™ X, Internal
cleaning and internal
drying
(Type U2, K2, Y2)
Normal (Life of refrigerant leak sensor hasn’t expired)
Life of refrigerant leak sensor has expired
Reset the life notification of refrigerant leak sensor in indoor unit (J04, J06)
Reset the refrigerant leak alarm (P08)
nanoe™ X OFF. Internal cleaning with nanoe™ X OFF Internal drying OFF.
0001
nanoe™ X ON. Internal cleaning with nanoe™ X ON Internal drying OFF.
(Not operational if R/C adaptable to the nanoe™ X not connected)
0002
nanoe™ X ON. Internal cleaning with nanoe™ X ON Internal drying OFF.
(Operational even if R/C adaptable to the nanoe™ X not connected)
0004
nanoe™ X ON. Internal cleaning with nanoe™ X OFF Internal drying ON.
(Operational even if R/C adaptable to the nanoe™ X not connected)
0005
nanoe™ X ON. Internal cleaning with nanoe™ X OFF Internal drying OFF.
(Operational even if R/C adaptable to the nanoe™ X not connected)
0006
nanoe™ X OFF. Internal cleaning with nanoe™ X OFF Internal drying ON.
(Operational even if R/C adaptable to the nanoe™ X not connected)
Internal cleaning dry
times
(when humidity is over
70%)
(Type U2, K2*)
(Type U2, K2*)
0000 Without fan operation
0001 1 minute
0002 2 minute
0118 118 minute
0119 119 minute
0120 120 minute
Internal cleaning dry
times
R32 refrigerant leakage
detection sensor
(when humidity is less
than 70%)
(FB)
* Type 45, 56, 73, 106
0000 Without fan operation
0001 1 minute
0002 2 minute
0118 118 minute
0119 119 minute
0120
0000
0001
120 mi
Not connected (Setting at shipment)
Connected (Automatically set by connecting to R32 refrigerant leakage
detection sensor)
nute
SM830289-01_欧州向け R32 mini VRF 8,10HP SM&TRSM.indb 17SM830289-01_欧州向け R32 mini VRF 8,10HP SM&TRSM.indb 17 2021/05/07 10:16:192021/05/07 10:16:19