Mini VRF SYSTEM
Control Functions - Outdoor unit
1
11. Detailed Settings in EEPROM of Outdoor
Unit
Never use the DN code unlisted in the following table. (P) : Factory preset mode
DN Item Setting No.
05 Outdoor fan silent mode
0=Invalid (P) 1=Silent mode 1
2=Silent mode 2,,,,, 15=Silent mode 15
(For details, see Section "4. Outdoor Unit Fan Control (6)")
06 Defrost fan speed select 0=Invalid (P) , 1=LL fan speed
0C Indoor unit drain pump forced operation
0=Invalid (P)
1=stop for 2 hours and drive for 20 minutes constantly
2=stop for 20 minutes and drive for 20 minutes constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF
(For details, see Section "5. Outdoor Unit CCU Control (4)")
0D
Measures against smell when indoor unit cooling
thermostat OFF
0=Invalid (P)
1=Measures against smell
19
Setting of control validity range when pressing the
Energy saving button
0=for group (P)
1=for refrigerant system
(For details, see Section “9. Demand Control (2)”)
1A Demand 1 current (%)
0=0% 40=40%
45=45%,,,,, 100=100% (P) ,,,,,
130=130% -1=No control
(For details, see Section "9. Demand Control")
1B Demand 2 current (%)
0=0% 40=40%
45=45%,,,,, 70=70% (P) ,,,,,
130=130% -1=No control
(For details, see Section "9. Demand Control")
1E Demand remote controller display
0=No demand display
1=When demand ON, “demand - actived” display (P)
2=When forced thermostat OFF with demand ON,
“demand - actived” display
(For details, see Section "9. Demand Control")
24 Indoor unit self oil recovery control
0=fan stop (P)
1=fan operate & Te +5°C shift (For Type D, K)
(For details, see Section “6. Oil Control (5)”)
27
Auto Cooling / Heating Functions mode change mask
time
0=Invalid (P) 30=30 minutes
40=40 minutes ,,,,, 240=240 minutes
(For details, see Section "10. Other Functions (1)")
2A Dew condensation prevention control of indoor unit
0=Invalid (P) 1=30 minutes
2=40 minutes 3=50 minutes
4=60 minutes
2B DP operation time for slime measures
20=20 minutes 30=30 minutes (P)
40=40 minutes 50=50 minutes
60=60 minutes
(For details, see Section "5. Outdoor Unit CCU Control (4)")
2C Indoor unit fan stop temperature shift -10=-10°C,,,,, 0=+0°C (P) ,,,,,20=20°C
35
Condensation temperature adjustment
Lower temperature of B area (Tc_B) for heating mode
-7=-7°C -6=-6°C,,,,, 0=0°C (P) ,,,,, 7=7°C
36
Condensation temperature adjustment
Upper temperature of B area (Tc_B) for heating mode
-7=-7°C -6=-6°C,,,,, 0=0°C (P) ,,,,, 7=7°C
3E PSccutgt delay-start setting
0=8 second delay-start (P)
1=(system address x1x8) second delay-start
2=(system address x2x8) second delay-start
3=(system address x3x8) second delay-start
3F Evaporating temperature control lower limit shift -5=-5°C,,,,,0=0°C (P), 1=1°C,,,,,11=11°C
40 Evaporating temperature control upper limit shift -5=-5°C,,,,,0=0°C (P), 1=1°C,,,,,11=11°C
51
Indoor unit fan's intermittent operation and operating
time when in cooling thermostat OFF
30=30 seconds , 60=60 seconds (P) ,,,, 240=240 seconds
52
Indoor unit fan's intermittent operation and stopped
time when in cooling thermostat OFF
5=5 minutes (P), 10=10 minutes, 15=15 minutes, 20=20 minutes,
25=25 minutes, 30=30 minutes