EasyManua.ls Logo

Panasonic LZ2 - Page 52

Panasonic LZ2
183 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mini VRF SYSTEM
Control Functions - Outdoor unit
1 - 28
1
10. Other Functions
(2) Setting when at Thermostat OFF in Cooling Mode
When decreasing the indoor airow volume at the cooling thermostat OFF or dry thermostat OFF, follow the setting
procedure below.
EEPROM setting in outdoor unit
CODE: ED
Setting No. Indoor fan mode
Indoor unit
expansion valve
Louver
0 (factory preset mode) w/o force w/o force w/o force
1 STOP *3 20 w/o force
2 LL 20 w/o force
3 Interval mode *4 20 w/o force
4 Never use - -
*1 If setting at thermostat ON, the system will return to the normal indoor fan control or solenoid valve kit mode.
*2 Whenever changing thermostat ON and OFF, solenoid valve kit sounds ON and OFF.
*3 When setting at Stop mode, be sure to set the room sensor to the remote control thermostat.
EEPROM setting in outdoor unit
CODE: 32
Setting No.
0 Indoor unit sensor (factory preset mode)
1 Remote control sensor
*4 Operation when in the intermittent airow setting
When in the thermostat OFF, LL airow and stop mode repeats alternately and the mechanical valve and
solenoid valve kit remain in the forced condition.
• Interval intermittent operation can be changed by EEPROM setting.
EEPROM setting in indoor unit
CODE: 51
Setting No.
Indoor unit fan operating
time [sec]
30 30
60 (factory preset mode) 60
90 90
210 210
240 240
CODE: 52
Setting No.
Indoor unit fan stopped
time [min]
5 (factory preset mode) 5
10 10
15 15
20 20
25 25
30 30
SM830289-01_欧州向け R32 mini VRF 8,10HP SM&TRSM.indb 28SM830289-01_欧州向け R32 mini VRF 8,10HP SM&TRSM.indb 28 2021/05/07 10:10:302021/05/07 10:10:30

Table of Contents

Related product manuals