3. Different tools required
3-1. Tool specifications have been changed due to the characteristics of R32.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
Item
Different
tools?
(From
R22 and
R407C)
R410A tools
compatible
with R32?
Remarks
Manifold gauge Yes Yes
Types of refrigerant, refrigerating machine oil,
and pressure gauge are different.
Charge hose Yes Yes
To resist higher pressure, material must be
changed.
Vacuum pump Yes Yes
Use a conventional vacuum pump if it is
equipped with a check valve. If it has no check
valve, purchase and attach a vacuum pump
adapter.
Leak detector Yes Yes
Leak detectors for CFC and HCFC that react
to chlorine do not function because R32 and
R410A contains no chlorine. Leak detectors for
HFC can be used for R32 and R410A.
Flaring oil Yes Yes
For systems that use R22, apply mineral oil
(Suniso oil) to the flare nuts on the tubing to
prevent refrigerant leakage. For machines that
use R32 or R410A, apply synthetic oil (ether oil)
to the flare nuts.
* Using tools for R22, R407C, R410A and R32 together can cause defects.
Manifold gauge Vacuum pump
Inlet
Single-outlet valve
(with siphon tube)
Liquid refrigerant should be recharged
with the cylinder standing on end as
shown.
Valve
Liquid
00_330344_2WAY_Eng.indb 19 2020/12/21 11:26:34
Important Information Regarding The Refrigerant Used
This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere.
Refrigerant type: R32
GWP
(1)
value: 675
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required depending on European or local
legislation.
Please contact your local dealer for more information.
Please fill in with indelible ink,
1: the factory refrigerant charge of the product
2: the additional refrigerant amount charged in the field
1 + 2: the total refrigerant charge
(1 + 2) x 3/1000: CO
2
equivalent in tons; multiply the total refrigerant charge by GWP
value, then divided by 1000.
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the
inside of the service cover).
1. Factory refrigerant charge of the product: see unit name plate
2. Additional refrigerant amount charged in the field*
3. Total refrigerant charge
4. Contains fluorinated greenhouse gases
5. Outdoor unit
6. Refrigerant cylinder and manifold for charging
7. GWP(global warming potential) of the refrigerant used in this product
8. CO
2
equivalent of fluorinated greenhouse gases contained in this product
* English text printed on this label is original.
Each language label will be sealed on this original text.
4
567
This product contains fluorinated greenhouse gases.
CO
2
equivalent amount is shown in “CO
2
eq.
1
2
“CO
2
eq.”
1 000
( ) x
+
1 2 3
1
1
kg
2
2
kg
1 2
3
kg
8
ton
R32
GWP : 675
3
00_330344_2WAY_Eng.indb 20 2020/12/21 11:26:34