2
2
2-7
2-8-4. Indicating (marking) the Indoor and Outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure
that the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit
control PCB, and use a magic marker or similar means which cannot be easily erased to indicate the numbers
in an easily visible location on the indoor units (near the indoor unit nameplates).
Example: (Outdoor) 1 - (Indoor) 1
(Outdoor) 2 - (Indoor) 1
(2) These numbers will be needed for maintenance. Be sure to indicate them.
* Use the remote controller to check the addresses of the indoor units. Press and hold the
button and
button for 4 seconds or longer (simple settings mode).
Then press the
button and select the indoor address. (Each time the button is pressed, the address
changes as follows: 1-1, 1-2, ... 2-1, 2-2, ....) The indoor unit fan operates only at the selected indoor unit.
Confirm that correct fan is operating, and indicate the address on the indoor unit.
Press the
button again to return to the normal remote controller mode.
For details, refer to the separate manual.
2-8-5. Main-sub remote controller control
Control using 2 remote controller switches Main-sub remote controller control refers to the use of 2 remote
controllers to control 1 or multiple indoor units. (A maximum of 2 remote controllers can be connected.)
Connecting 2 remote controllers to control 1 Indoor unit
1 2
1 2
1 2
U1U2
1 2
Remote controller setting mode
To set the remote controller main/sub setting or change the sensor, follow the steps below.
RCU. Main/Sub
MainSub
CODE
ITEM
DATA
ITEM
Clock display
12 hours
(AM/PM)
24 hours
RCU. CK
NormalRCU. CK
Room temperature sensor
Main unit RCU
Remote controller wiring
Terminal plate for remote
controller wiring
switch (main)
Optional
Optional
Remote controller
switch (sub)
Ground
Ground
Indoor unit
Outdoor unit
(1) Press both and buttons on the remote controller for more than 4 seconds together.
(2) Select CODE No. with / ( ) buttons.
(3) Change DATA with / (TIMER) buttons.
(4) Press
. Finally, press .
DATA is memorized in the RCU. (DATA setting will
not be changed even when the power is turned off.)
Make sure to set [Normal] for RCU. CK.