22
2-3-1-11
(3)(1) (4)
(4)
* Auto address setting in Cooling mode cannot be done from the remote controller.
Auto Address Setting* from the Remote Controller (CZ-RTC4)
NOTE
Selecting each refrigerant system individually for auto address setting
Auto address setting for each system : Item code “A1”
button and
/
(1) Press the remote controller timer time
button at the same time.
(Press and hold for 4 seconds or longer.)
(2) Next, press either the temperature setting
(Check that the item code is “A1”.)
button.
(3) Use either the
auto address setting.
button to set the system No. to perform
Select the “O/D unit no.” by pressing the
or button.
2-3-1-6-3. Auto Address Setting Using the Remote Controller
Auto Address Setting from the High-spec Wired Remote Controller (CZ-RTC5B)
Select one of the “O/D unit no.” for auto address
by pressing the
or button.
Approximately 10 minutes are required.
When auto address setting is completed, the units
return to normal stopped status.
20:30 (THU)
[ ]
START
CZ-RTC5B
(1)
CZ-RTC4
Keep pressing the , and buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD display.
If you wish to see the next screen instantly, press the
Press the )2(
or button to see each menu.
or button.
Select “9. Auto address” on the LCD display and press
the button.
Maintenance func
Sel.
20:30 (THU)
Page [ ] Confirm
9. Auto address
10. Set elec. consumption
11. Set touch key
12. Check touch key
(3) The “Auto address” screen appears on the
Auto address
LCD display.
Change the “Code no.” to “A1” by pressing
the
or button.
O/D unit no.Code no.
20:30 (THU)
Sel. Next
1
A1
(4) Then press the button.
(Auto address setting for one refrigerant system begins.)
(When auto address setting for one system is completed,
(2)
the system returns to normal stopped status.)
<Approximately 4 – 5 minutes is required.>
(During auto address setting, “
” is displayed on
the remote controller.
This message disappears when auto address setting is completed.)
(5) Repeat the same steps to perform auto address setting for each successive system.
(4)
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 11 2020/01/29 19:52:18