A simplified installation is shown below. This installation is not EMC compliant. For European
installations and countries with EMC legislation refer to the 890 Engineering Reference Manual,
Appendix C.
* Permanent Earthing
The unit must be permanently earthed according to EN 50178: For
permanent earthing, one conductor, PE1, of >10mm² cross-section is
required; or two individual incoming protective earth conductors, PE1 &
PE2, of <10mm² cross-section. Each earth conductor must be suitable for
the fault current according to EN 60204.