Page 12
890SD Frame F Power Connections
Connect motor leads to M1/U, M2/V, M3/W.
Maximum wire sizes::
Frame F: 95mm
2
/ 4/0AWG (without crimp)
95mm
2
/ 4/0AWG (with crimp)
Connect the earth/ground wire from the terminal
box of the motor directly to the earth/ground
terminal.
Maximum wire sizes:
Frame F: 95mm
2
/ 4/0AWG (without crimp)
95mm
2
/ 4/0AWG (with crimp)
If not using shielded cable, run motor leads in an
enclosed metal conduit bonded to the drive at
one end and the motor at the other.
Connect the earth/ground wire to the
earth/ground terminal.
Maximum wire sizes:
Frame F: 95mm
2
/ 4/0AWG (without crimp)
95mm
2
/ 4/0AWG (with crimp)
Connect the 3-phase supply.
Maximum wire sizes:
Frame F: 95mm
2
/ 4/0AWG (without crimp)
95mm
2
/ 4/0AWG (with crimp)
Connect the 115 or 220Vac auxiliary
supply for the internal fans to AUX 1 and
AUX 2 (in any order).
See block 5 of the Model Number:
1F = 115Vac, 2F = 220Vac.
Connect the brake resistor.
Maximum wire sizes:
Frame F: 95mm
2
/ 4/0AWG (without crimp)
95mm
2
/ 4/0AWG (with crimp)
An External Braking Resistor is optional.
Connect it between DBR+ and DBR- for
high inertial loads.
DO NOT apply external voltage sources
(mains supply or otherwise) to the braking
terminals.
We recommend using a thermal overload
switch to protect the braking circuit.
5
6
5
6
7
Bond the motor cable
screen to the drive and
motor, as close as
possible to both terminals
PE1
Terminate all
control cable screens
using a gland at the
gland plate
auxiliary
supply
terminals
(fan)
M1/U M2/V M3/W
3-Phase Supply
Motor
8
L1 L2 L3
9
brake
resistor
terminals