Programming D-80
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
If not, apply a compensation using the ELEC POS OFFSET parameter. If necessary, repeat steps 6 and 7 until an error
of only 1° to 5° is achieved.
Examples:
In U phase (90°), if ELEC POS = 20° then ELEC POS OFFSET must be set to 70° to get a value of 90° for ELEC POS.
In U phase (90°), if ELEC POS = -160° then ELEC POS OFFSET must be set to 110° ( +250° ) to get a value of 9
for ELEC POS. 90° is equivalent to 270°, which explains the value of 110° : -270° = -160° + (-110°).
10. Verify the correct value of ELEC POS parameter and set POLARISATION = DISABLE, POLAR START = FALSE.
This function could also be used to verify the correct connection of the motor phase (correct succession of the 3 phases) by :
1. Polarise the motor on the U phase with a low current, typically 20 to 30%, and a ramp value of 1 second.
2. Change the phase to V, then W, etc. using the MOTOR PHASE parameter and apply torque to the motor:
If the motor is rotating in a clockwise direction, looking to the front shaft of the motor, then the motor phases
are connected correctly. (With the encoder correctly wired, the encoder position will increment when the motor
turns in a clockwise way looking to the front shaft of the motor)
If the motor is rotating in a counter clockwise direction, looking to the front shaft of the motor, two of the
motor phases must be inverted, for example U and V phases.