EasyManua.ls Logo

Parker ac890 - Page 617

Parker ac890
711 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-221
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
2PREF Name Block Type Range Default ro\rw Notes
83.07 FAST STOP T-LIM TORQUE LIMIT REAL 0.00 to 300.00 % 150.00 % rw
84.01 AIMING POINT INVERSE TIME REAL 50.00 to 105.00 % 105.00 % rw
84.02 DELAY INVERSE TIME REAL 5.0 to 60.0 s 60.0 s rw
84.03 DOWN TIME INVERSE TIME REAL 1.0 to 10.0 s 10.0 s rw
84.04 UP TIME INVERSE TIME REAL 1.0 to 600.0 s 120.0 s rw
84.05 IT LIMITING INVERSE TIME BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
84.06 INVERSE TIME OP INVERSE TIME REAL _.xx 150.00 % ro Output
84.08 IT WARNING INVERSE TIME BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
85.01 HYSTERISIS ZERO SPEED REAL 0.00 to 300.00 % 0.10 % rw
85.02 THRESHOLD ZERO SPEED REAL 0.00 to 300.00 % 0.50 % rw
85.03 AT ZERO SPD FBK ZERO SPEED BOOL 0 : FALSE
1 : TRUE
TRUE ro Output
85.04 AT ZERO SPD DMD ZERO SPEED BOOL 0 : FALSE
1 : TRUE
TRUE ro Output
85.05 AT STANDSTILL ZERO SPEED BOOL 0 : FALSE
1 : TRUE
TRUE ro Output
91.01 INPUT SKIP
FREQUENCIES
REAL -300.00 to 300.00 % 0.00 % rw
91.02 BAND 1 SKIP
FREQUENCIES
REAL 0.0 to 500.0 Hz 0.0 Hz rw
91.03 FREQUENCY 1 SKIP
FREQUENCIES
REAL 0.0 to 500.0 Hz 0.0 Hz rw
91.04 BAND 2 SKIP
FREQUENCIES
REAL 0.0 to 500.0 Hz 0.0 Hz rw
91.05 FREQUENCY 2 SKIP
FREQUENCIES
REAL 0.0 to 500.0 Hz 0.0 Hz rw