D-257
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
2PREF Name Block Type Range Default ro\rw Notes
161.03 I2T MOTOR LOAD MOT PMAC
PROTECT
REAL _.x 0.0 % ro Output
161.04 MOTOR I2T TRIP MOT PMAC
PROTECT
BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
161.05 ENABLE MOT PMAC
PROTECT
BOOL 0 : FALSE
1 : TRUE
TRUE rw
162.01 AIMING POINT INVERS TIME
PMAC
REAL 25.00 to 105.00 % 105.00 % rw
162.02 DELAY INVERS TIME
PMAC
REAL 0.5 to 60.0 s 4.0 s rw
162.03 DOWN TIME INVERS TIME
PMAC
REAL 0.5 to 10.0 s 1.0 s rw
162.04 UP TIME INVERS TIME
PMAC
REAL 0.5 to 10.0 s 1.0 s rw
162.05 IT LIMITING INVERS TIME
PMAC
BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
162.06 INVERSE TIME OP INVERS TIME
PMAC
REAL _.xx 0.00 % ro Output
162.07 IT WARNING INVERS TIME
PMAC
BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
163.01 SELECT TQ COMP
2
SPEED LOOP 2 ENUM 0 : NONE
1 : MAX ATTENUATION
2 : MINIMUM PHASE
3 : NOTCH FILTER
NONE rw 2
163.02 TQ COMP 2 FREQ SPEED LOOP 2 REAL 100 to 8000 Hz 2000 Hz rw
163.03 SELECT TQ COMP
3
SPEED LOOP 2 ENUM 0 : NONE
1 : MAX ATTENUATION
2 : MINIMUM PHASE
3 : NOTCH FILTER
NONE rw 2
163.04 TQ COMP 3 FREQ SPEED LOOP 2 REAL 100 to 8000 Hz 2000 Hz rw