D-261
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
2PREF Name Block Type Range Default ro\rw Notes
182.03 BAUD RATE MODBUS RTU ENUM 0 : UNKNOWN
1 : 1200
2 : 2400
3 : 4800
4 : 7200
5 : 9600
6 : 14400
7 : 19200
8 : 38400
9 : 57600
10 : 115200
UNKNOWN ro Output
182.04 DATA BITS MODBUS RTU INT _ 0 ro Output
182.05 PARITY MODBUS RTU ENUM 0 : NONE
1 : ODD
2 : EVEN
NONE ro Output
182.06 STOP BITS MODBUS RTU ENUM 0 : UNKNOWN
1 : ONE
2 : TWO
UNKNOWN ro Output
182.07 TIMEOUT MODBUS RTU REAL _. 0 ms ro Output
182.08 WORD ORDER MODBUS RTU ENUM 0 : LOW WORD FIRST
1 : HIGH WORD FIRST
LOW WORD FIRST ro Output
182.09 RX GOOD COUNT MODBUS RTU INT _ 0 ro Output
182.10 LAST TX STATUS MODBUS RTU ENUM 0 : OK
1 : ILLEGAL FUNCTION
2 : ILLEGAL ADDRESS
3 : ILLEGAL DATA VAL
4 : SLAVE DEVICE FAIL
5 : ACKNOWLEDGE
OK ro Output