TTrraaddiittiioonnaall  HHyyddrraauulliicc  VVaallvvee  CCoonnttrrooll  eeqquuiivvaalleenntt  
VVaallvvee  MMooddee  11  
Through Keypad Entry the user may change the default value "0"  to  "1" allows a infinite variable speed adjustment with 
a 0-10V DC analog Input.  This setting will changeable on the fly.  See page 19 for details on how to change mode.
Enable, Clockwise (CW), Counter-Clockwise (CCW), Extend and Retract Limits are fully functional in this operation 
mode.  
When increasing speed setting- acceleration or Ramp Rate (R1) is used to ramp from current speed to new analog 
setting.  When decreasing speed setting, deceleration or Ramp Rate (R2) is used to ramp from current speed to new 
analog setting.  Ramp (R1, R2) settings are adjusted through keypad entry. See page 32-33 for more detail.
NNoottee::    The  range  of  input  is  scaled  to  ensure  minimum  pump  speed  is  maintained  for  proper  operation.  The  speed 
range is set by the Pump displacement from the HAS Ordering Code.  The Macro also includes a 1% of total command 
set as dead band to prevent unwanted travel due to electrical noise imposed on input. 
Example 1: 3 cc pump (G03) ordering code, Max pump speed is 4000 RPM.  Min pump speed 500 RPM.  10V input 
equals 100% of max speed, while 5V input equates to 56% of max speed.  An input of 0.09V will be ignored and no 
motion generated. 
Example 2: 11 cc pump (G11) ordering code, Max pump speed is 2400 RPM.  Min pump speed 500 RPM.  10V input 
equals 100% of max speed, while 5V input equates to 60% of max speed.  An input of 0.09V will be ignored and no 
motion generated. 
This macro is useful when the desired motion needs to be changed infinitely from a master Programmable Logic 
Controller (PLC) or if speed Potentiometer is desired. 