Hydraulic and Electrohydraulic Actuators
HAS Series Analog Drives Manual
93
Parker Hannifin Corporation
Cylinder Division
Des Plaines, Illinois USA
www.parker.com/cylinder
Catalog HY08-4005-M3
WARNING: This product can expose you to chemicals including Lead and Lead Compounds which are known to the State of
California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
PROP 65 WARNING
Trip Table
66551111
KKeeyyppaadd
DDiissppllaayy
66990011
KKeeyyppaadd
DDiissppllaayy
DDeessccrriippttiioonn PPoossssiibbllee RReeaassoonn ffoorr TTrriipp
OC OVERCURRENT The motor current being
drawn from the drive is
too high
♦ Pressure too high
♦ Pump to big
♦ Application error
♦ Short circuit between motor phases
♦ Short circuit between motor phase and
earth
STO SAFE TORQUE OFF Safe Torque Off (STO) is
active.
♦ One or both STO user inputs is low
♦ A fault has been detected in the STO circuit
HOT HEATSINK
The drive heatsink
temperature is too
high
♦ The ambient air temperature is too high
♦ Poor ventilation or spacing between drives
ET EXTERNAL TRIP User trip caused via control
terminals
♦ +24V not present on external trip (terminal X15/05)
♦ Check setting of EXT TRIP MODE parameter
95