Hydraulic and Electrohydraulic Actuators
HAS Series Analog Drives Manual
Catalog HY08-4005-M3
98
WARNING: This product can expose you to chemicals including Lead and Lead Compounds which are known to the State of
California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
PROP 65 WARNING
Trip Table
66551111
KKeeyyppaadd
DDiissppllaayy
66990011
KKeeyyppaadd
DDiissppllaayy
DDeessccrriippttiioonn PPoossssiibbllee RReeaassoonn ffoorr TTrriipp
DBCT INT DB RESISTOR
Braking mode set to INTERNAL (future use only).
Set to EXTERNAL and connect an External
Braking Resistor if braking is required.
TRIP UNKNOWN
An unknown trip - refer to Parker Hannifin
Manufacturing
TR32 OTHER
Refer to OTHER in Appendix D: TRIPS STATUS.
One or more trips have occurred with a Value
greater than 32. See the list.
ATN1 MAX SPEED LOW
During Autotune the motor is required to run at the
nameplate speed o f the motor. If MAX SPEED
RPM limits the speed to less than this value, an
error will be reported. Increase the value of
MAX SPEED RPM up to the nameplate rpm of
the motor (as a minimum). It may be reduced,
if required, after the Autotune is complete.
ATN2 MAINS VOLTS LOW
The mains input voltage is not sufficient to carry out
the Autotune. Re-try when the mains have recovered.