PAGE 29
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODE SETTINGS SETTING SETTING
6 Output 2 Percent Limit o2PL 0 to 100 %
100
7 Output 3 out3 0=None
0
1=Process Alarm -
Direct
2=Process Alarm -
Reverse
3=Deviation Alarm -
Direct
4=Deviaiton Alarm -
Reverse
5=Deviation Band Alarm-
Open withing band
6=Deviaiton Band Alarm-
Closed within band
8 Relay A Assignment rLyA 0=Not Assigned
1
1=Assigned to Output 1
2=Assigned to Output 2
3=Assigned to Output 3
4=Assigned to Event 1
5=Assigned to Event 2
6=Assigned to Event 3
9 Relay B Assignment rLyb Same selection as Relay A
2
10 Relay C Assignment rLyC Same selection as Relay A
3
11 Display Select diSP 1=Process Value
1
2=Process Value & Setpoint
3=Process Value Deviation
4=Process Value Deviation &
Setpoint
5=Setpoint
12 Decimal Position dPoS 0 or 1 decimal place
0
(dPoS can be 2, 3, &4
if Euu is selected)
13 Engineering Units Euu -9999 to 9999 units
1000
Upper Value
14 Engineering Units EuL -9999 to 9999 units
0
Lower Value
15 Hysteresis HySt 0 to 300 degrees
3
(width of hysteresis band,
see Page 68)
16 Setpoint Upper Limit SPL -9999 to 9999 degrees
1400
(SPuL -EO option)
17 Setpoint Lower Limit SPLL -9999 to 9999 degrees
0
(EO Option)
18 Automatic Transfer AtFr 0=No automatic transfer
0
1=Transfer when
temperature goes
below setpoint
2=Transfer when
temperature goes
above setpoint
NOTE:
When changing the Decimal
position dPoS, the operator
MUST ensure that all values
previously programmed or
tuned are now valid with the
entry of a decimal point.