Two-Position and Floating Dampers:
Power-Open/Spring-Close - Page 19
Power-Close/Spring-Open - Page 20
Power-Open/Power-Close (Floating) - Page 20
Mixing Box - Page 21
Dual Duct - Page 23
Modulating Damper:
Single Damper: 0[2]–10 VDC - Page 21
Mixing Box: 0[2]–10 VDC - Page 22
Dual Duct: 0[2]–10 VDC - Page 24
Pelican thermostats and accessories can be wired and
configured to control a wide range of zone dampers.
Refer to the “ Intallation Planning” diagrams on pages 6
to 12 for the most common applications.
It is essential to follow these diagrams, as the
controller’s outputs are closely linked to their
configured functions. Verify proper mechanical
operation before and after installation and ensure that
all configurations are accurate for your installation.
For installations outside of these diagrams, stop what
you are doing and contact Pelican support for further
assistance.
AHU
SUPPLY
Pelican Thermostat
Discharge Air Sensor
(10K Type II)
PELICAN
TA1
7
6
(1)
OPEN
(2)
24V AC Damper
Actuator Terminals
(Typical)
2
2
3
4
1
5
COMMON
24 VAC POWER-OPEN
24V AC POWER
DATA
COMMON
POWER-OPEN
DAMPER ACTUATOR
Wiring - Damper Actuators
The zone thermostat sends 24V AC from [Y] to power
the damper open for heating, cooling, and ventilation
cycles. When 24V AC is removed, the dampers’ actuator
springs closed.
Note: As shown in the diagram, install a discharge air
sensor to ensure proper damper operation. Refer to
page 16 for detailed wiring diagrams of accessory.
24V AC Power-Open/Spring-Close
(Two-Position Damper Actuator)
19