◦ Power: 24V AC, 60 Hz, 105 mA
◦ Operating Voltages: 23 — 30V AC
◦ Number of Binary Outputs:
▪ TC1 & TC3: Five (5)
▪ TC2 & TC4: Seven (7)
◦ Binary Output Relay Ratings:
▪ Y, Y2, G, W, W2: 2.0 A Running
▪ Dh & Hu: 1.0 A Running
◦ Mounting: Designed to be mounted an a vertical
single gang electrical box or on a flat surface.
◦ Wireless: 2.4 GHz wireless frequency, IEEE 802.15.4
wireless standard. Complies with Class B Part 15 of
FCC rules. Does not interfere or communicate with
WiFi/802.11 networks. Pelican Mesh Network
Enabled.
◦ Temperature Deadband: 3°F differential setting
with auto-adjusting to 5°F anti-fighting.
◦ Operating Range: -4°F — 160°F @ 5 % — 90 %
Relative Humidity (non-condensing)
◦ Humidity Sensor (TC2 & TC4):
▪ Humidify setting: 10 - 80% RH
▪ Dehumidify setting: 20 - 90% RH
◦ Carbon Dioxide Sensor (TC3 & TC4): 400 - 2000
PPM detection range. +/- 50 PPM accuracy @ 600
PPM and 1000 PPM, auto-calibrating.
◦ Storage Temperature: -20°F — 160°F
◦ Dimensions:
▪ in: 5.2 X 3.9 X 0.75
▪ mm: 132 X 99 X 19
TC Thermostat Specifications
◦ Capabilities: Adds a temperature input to a Pelican
thermostat, most commonly used for discharge air
temperature detection.
◦ Power: 24V AC, 60 Hz, 50 mA
◦ Wiring to Thermostat: Three (3) low-voltage power
and communication wires.
◦ Operating Voltages: 23 — 30V AC
◦ Number of Thermistor Inputs: One (1)
◦ Thermistor Type: 10K Type II (77°F @ 10000 Ohms)
TA1 Accessory Specifications
◦ Zoning Capabilities: Adds modulating damper
and/or reheat control. Also provides a
temperatures inputs to a Pelican thermostat, most
commonly used for discharge air temperature
detection.
◦ Power: 24V AC, 60 Hz, 50 mA
◦ Wiring to Thermostat: Three (3) low-voltage power
and communication wires.
◦ Operating Voltages: 23 — 30V AC
◦ Number of Analog Outputs: Two (2)
◦ Analog Output Range: 0 [2] — 10V DC
◦ Number of Analog Inputs: Two (2)
◦ Analog Input Range: 0 [2] — 10V DC
◦ Number of Thermistor Inputs: Three (3)
◦ Thermistor Type: 10K Type II (77°F @ 10000 Ohms)
◦ Temperature Detection Range: -20°F — 180°F
◦ Mounting: Designed to be mounted at the zone
damper equipment it is controlling.
◦ Temperature Detection Range: -20°F to 180°F
◦ Operating Range: -4°F — 160°F @ 5 % — 90 %
◦ Storage Temperature: -20°F — 160°F
◦ Dimensions:
▪ in: 3.6 X 5.2 X 1.1
▪ mm: 91.4 X 142 X 28
PEARL Accessory Specifications
◦ Mounting: Designed to be mounted on a flat
surface.
◦ Temperature Detection Range: -20°F to 180°F
◦ Operating Range: -4°F — 160°F @ 5 % — 90 %
Relative Humidity (non-condensing)
◦ Storage Temperature: -20°F — 160°F
◦ Dimensions:
▪ in: 2.5 X 2.5 X 0.75
▪ mm: 63.5 X 63.5 X 19
3