Pelican TC Series - Temperature Settings; Thermostat Operation; Damper Settings

Pelican TC Series
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
¹For Dual Duct applications separate configurations for the cold
deck damper and hot deck damper control types will be available.
²Modulating options will automatically appear only if a PEARL is
wired to the thermostat.
¹Configuration appears if there is an external temperature sensor
wired to the thermostat. Reference “Configurations - Input Sensor”
on page 38 for more information.
²Configuration appears for thermostats with internal Carbon
Dioxide (CO2) sensors. For sequence of operation information
reference “Sequence of Operations - Demand Controlled
Ventilation” on page 45.
Configuration Name/Description Settings/Range
Heat Range – Sets the Heat To
set-point range allowance.
Generally restrictions to how high
the heat can be set is important for
operation and energy efficiency.
56°F to 76°F
-20°F to 180°F
(D)
(R)
Fahrenheit
Celsius
(D)
Enabled
Disabled
(D)
Enabled
Disabled
(D)
66°F to 86°F
-20°F to 180°F
(D)
(R)
Temp Display – Sets which units
the temperature will be displayed
in on the thermostat.
Temp Sensor¹ – Disables or
enables the thermostats internal
temperature sensor.
Cool Range – Sets the Cool To
set-point range allowance.
Generally restrictions to how low
the cool can be set is important for
operation and energy efficiency.
800
400 - 2000
(D)
(R)
CO2 Ventilation² – Sets at which
CO2 parts per million (PPM) level
demand ventilation will start.
Display CO2² – Disable or enable if
the thermostat displays to current
CO2 reading in its Info screen.
Thermostat Operation
Adjust sequences for maintaining room temperature.
Configuration Name/Description Settings/Range
Cycles Per Hour – Sets a target
cycle rate for the thermostat.
4
1 to 6
(D)
(R)
0°F
-2.0°F to 2.0°F
(D)
(R)
0.1°F
0.0°F to 0.5°F
(D)
(R)
Calibration Degrees – Adjusts the
thermostats internal temperature
reading.
Yes
No
(D)Satisfy Cooling with Aggressive¹
(advanced) – Disables or enables if
aggressive cooling remains
advertised when the zone
temperature is within 1.0°F of the
cool set-point.
Anticipation Degrees – Adjusts
the deviation above or below
set-point before starting a purge
cycle.
Configurations
Damper Settings
Configure what type of zone damper and reheat the
thermostat is controlling.
Configuration Name/Description
Damper Type¹ – Enables the
correct outputs for the type of
damper actuator being controlled.
None
Open/Close
Floating
Mixing Box
Modulating²
Modulating Mixing
Box²
(D)
Fan Control (advanced) – Enables
the control sequence for a Parallel
or Series terminal fan powered
box.
None
Parallel
Series
(D)
Dump Zone (advanced) – Enables
intelligent dumping for capacity
management sequences.
Limited
No
Yes
(D)
¹Sateify Cooling with Aggressive set to YES: If the zone temperature
transitions from modurate cooling demand to aggressive cooling
demand it will continue to advertise aggressive cooling demand to
eliminate its need for cooling.
Sateify Cooling With Aggressive set to NO: If the zone temperature
transitions from modurate cooling demand to aggressive cooling
demand it will switch to advertising modurate cooling demand and
not remain in aggressive.
Settings/Range
Temperature Settings
Adjust temperature set-point ranges and sensor usage.
36