Actuator Travel Time – Sets how
many seconds it takes to rotate the
damper from full closed to full
open.
Floating Damper Configurations:
Ventilation Damper Position
Sets the position to rotate the
damper to during ventilation
cycles.
Maximum Damper Position – Set
the position to rotate the damper
to during heating, cooling, and
reheat cycles.
Damper Signal Output – Sets
which analog output is used for
damper modulation.
(blank)
1 to ??
(D)
(R)
(blank)
0% to 100%
(D)
(R)
100%
0% to 100%
(D)
(R)
A1
A2
(D)
Modulating Damper Configurations³:
Damper Settings Continued...
10.0V DC
0.0 to 10.0
Open¹: (D)
(R)
2.0V DC
0.0 to 10.0
Closed²: (D)
(R)
Damper Actuator Voltages – Sets
the volt [DC] range for the
modulating damper.
¹For mixing box applications, this will be labeled “Cold” which will
be the output voltage to rotate towards the cold deck.
²For mixing box applications, this will be labeled “Heat” which will
be the output voltage to rotate towards the hot deck.
³Modulating Damper Configurations will automatically appear only
if a PEARL is wired to the thermostat and if the Damper Type is set
to one of the modulating options.
Configurations
Economizer (turn OFF)
When a PEARL is connected to a thermostat, this
configuration option appears. Make sure to turn OFF the
economizer sequences, as they are not used in damper
control operations.
Configuration Name/Description
Cool Fan Speed – Sets the fan
speed during moderate cooling
cycles.
70%
0% to 100%
(D)
90%
0% to 100%
(D)Cooling Speed - Stage 2 – Sets the
fan speed during aggressive
cooling cycles.
70%
0% to 100%
90%
0% to 100%
50%
0% to 100%
(D)
(D)
(D)
Heat Fan Speed – Sets the fan
speed during moderate heating
cycles.
Ventilation Fan Speed – Sets the
fan speed during ventilation cycles.
Settings/Range
Heat Speed - Stage 2 – Sets the fan
speed during aggressive heating
cycles.
Configuration Name/Description
Heat Size – Sets the energy
consumption when the moderate
heating is enabled.
Heat 2 Size –Sets the energy
consumption when the aggressive
heating is enabled.
Cool Size – Sets the energy
consumption when the moderate
cooling is enabled.
Cool 2 Size – Sets the energy
consumption when the aggressive
cooling is enabled.
Settings/Range
(blank)
Variable input
(D)
(R)
(blank)
Variable input
(D)
(R)
(blank)
Variable input
(D)
(R)
(blank)
Variable input
(D)
(R)
Zone Size Identifies a general size
(CFM) for this zone. Used for
capacity management sequences.
Medium
Small
Large
Extra-Large
(D)
(R)
Power Consumption
Provides settings for the consumption of different
demand states.
BTU - British Thermal Units - most common for gas
furnaces and hot water.
TON - Tonnage - most common for compressor stages
and chilled water.
KW - Kilowatt - most accurate if true kilowatt
consumption is known for each stage.
WATT - Watt - most accurate if true watt of consumption
is known for each stage.
Variable Speed Fan
When a PEARL is connected to a thermostat, this option
appears. It is rarely used in damper control but can
control a modulating fan terminal box. The PEARL's (A2)
output regulates fan speed, ranging from 0.0 VDC (0%)
to 10.0 VDC (100%)
37