0(2) – 10 VDC Position Signal
(Modulating Reheat Actuator)
Pelican Thermostat
24V AC POWER
DATA
Discharge Air Sensor
(10K Type II)
PELICAN
PEARL
T1
A1
A2
COMMON
(3) (2) (1)
24V AC / Modulating
Reheat
Actuator Terminals
(Typical)
3
2
COMMON
24 VAC POWER
0[2]–10 VDC IN
The PEARL uses DC voltage to adjust the reheat valve
position. Voltage settings for open and closed positions
are configured through the Pelican Connect app.
Note: As shown in the diagram, a discharge air sensor
is required for proper reheat operation. Refer to page
17 for detailed wiring diagrams of accessory.
AHU
SUPPLY
HOT WATER
REHEAT COIL
7
Wiring - Reheats
Electric Reheat
(Start/Stop)
The zone thermostat sends 24V AC from [W] to enable
the electric reheat during heating cycles. When 24V AC
is removed, the reheat is disabled.
Note: As shown in the diagram, install a discharge air
sensor to ensure proper reheat operation. Refer to
page 16 for detailed wiring diagrams of accessory.
AHU
SUPPLY
AIRFLOW
PROOVING
SWITCH
Pelican Thermostat
24V AC POWER
DATA
Discharge Air Sensor
(10K Type II)
PELICAN
TA1
7
COMMON
3
2
COMMON
START/STOP INPUT
ELECTRIC
REHEAT COIL
NEUTRAL
VOLTAGE
24 VAC
RELAY
6
2
6
2
1
11
12
4
4
10
9
27