Installer manual Siata V132 - SFE - Programming
Ref. MKT-IM-003 / B - 19.04.2017 49 / 88
Number of regenerations before a salt alarm is generated
Set the number of regenerations before a salt alarm is generated.
A Use and to edit this parameter.
B Press to validate and switch to the next parameters.
The following formula is used to calculate the number of regenerations before a salt alarm is
generated :
SA = [(M.xxx) x 1000] / [(L.xxx) x (G.xx)]
where :
M.xxx: amount of salt found in the brine tank [kg];
L.xxx: volume of resin [l];
G.xxx: amount of salt required to regenerate 1 liter of resin [g/l].
The result must be typed, rounded down to the closest integer.
Days of interval for the mandatory regeneration
Set the number of days of interval for the mandatory regeneration. If
this parameter is set to Off, the function is disabled.
A Use and to edit this parameter.
B Press to validate and switch to the next parameters.
Note
Regeneration will take place at the regeneration time even if the day is disabled.
Frequency
Set the frequency of the mains to 50 or 60 Hz.
A Use and to edit this parameter.
B Press to validate and switch to the next parameters.
Duration of the cycle end pulse
Set the duration of the cycle end pulse.
A Use and to edit this parameter.
B Press to validate and switch to the next parameters.
Note
This functionality only works if the controller has cycle end pulse.