Installer manual Siata V132 - SFE - Operation
56 / 88 Ref. MKT-IM-003 / B - 19.04.2017
8. Operation
8.1. Recommendations
Use only regeneration salts designed for water softening EN973.
For optimal system operation, the use of clean salt free from impurities is recommended (for
example salt pellets).
Do not use ice melt salt, block, or rock salts.
The sanitizing process (both with liquid and electrochlorination) may introduce chlorine
compounds which may reduce the life of the ion exchange resins. Refer to media manufacturer
specs sheets for more information.
8.2. Manual regeneration
To initiate a manual regeneration :
A Press and hold for 5 seconds.
→ The SFE controller can be used to either start regeneration immediately or delay it until the
programmed time.
BUse to scroll between immediate regeneration or
delayed regeneration at the programmed time.
CConfirm with .
→ When Delayed manual regeneration is chosen, the current
day of the week and the service icon will blink until regeneration
starts.
8.3. Cancelling a regeneration
A If a regeneration has started, the regeneration can be cancelled by pressing for 5 seconds.
→ The controller will then place the valve back in the service position.
8.4. Microswitch search
When powered on, the module may sometimes display F1-| or F2-|, where the number indicates the
first or second microswitch attempt. A rotating bar is also shown to indicate that the motor is on. If
both searches fail, the message FR01 is displayed.
8.5. Salt recharge
The controller has a counter that decreases by one at each regeneration. When the counter reaches
0, a salt alarm is generated. To recharge the counter to the initial value of the parameter SA, press
and hold when the module is in service, “SAL” will flash on the display for 5 seconds and the
counter will be reset to the setup value.