19
Alarm Messages
The control board can display specific alarm conditions. The table below shows the potential alarm messages on the
display.
Press ON/OFF to reset an alarm.
Timer/ Counter Menu messages
Within the service menu it is possible to access diagnostic data reflecting the runtimes and number of cycles that a
specific output has been activated. Press the Up and Down arrows simultaneously.. Press the MENU SELECT button
repeatedly until the display shows
Use the up and down arrows to display the different messages.
Press POOL/SPA to exit this menu.
COMP RUN TIME Displays current compressor runtime
COMP CYCLES Displays number of compressor cycles since last reset
COMP LOG TIME Displays total compressor runtime since last reset
FAN RUN TIME Displays current fan runtime
FAN CYCLES Displays number of fan cycles since last reset
FAN LOG TIME Displays total fan runtime since last reset
REV VLV RUN TIME Displays current reversing valve runtime
REV VLV CYCLES Displays number of reversing valve cycles since last reset
REV VLV LOG TIME Displays total reversing valve runtime since last reset
FLT PMP RUN TIME Displays current autoset/extend relay runtime
FLT PMP CYCLES Displays number of autoset/extend relay cycles since last reset
FLT PMP LOG TIME Displays total autoset/extend relay runtime since last reset
DEFROST RUN TIME Displays current defrost runtime
DEFROST CYCLES Displays number of defrost cycles since last reset
DEFROST LOG TIME Displays total defrost runtime since last reset
COMP WARRANTY Displays total compressor runtime (cannot be reset)
REV VLV WARRANTY Displays total reversing valve runtime (cannot be reset)
DEFROST WARRANTY Displays total defrost runtime (cannot be reset)
RUN TIMES/COUNTS
↑
OR
↓
TO VIEW
HIGH WATER TEMP Water temperature is above 40°C
LOW WATER TEMP Water temperature is below 7°C
LOW WATER FLOW The switch sensing water flow is open.
REMOTE POOL SPA Pool and Spa relay remote inputs are simultaneously energized.
Water temperature thermistor circuit shorted.
WATER THERM OPEN Water temperature thermistor circuit open.
SUCTION TH SHORT Defrost thermistor circuit shorted
SUCTION TH OPEN Defrost thermistor circuit open.
BROWNOUT The 24 VAC supply voltage to the control board is low.
HIGH REFRIG Refrigerant high pressure switch is open.
LOW REFRIG Refrigerant low pressure switch is open.
FIVE ALARMS
Indicates that 5 faults have occurred in one hour. This fault will automatically reset
in one hour or can be manually reset by pressing the ON/OFF button.
Problem with RS485 communication from IntelliPool