5sec.
5sec.
DISPLAY PARAMETERDEFAULT
0000
3
00:30
Gas:0.25” (0.63mbar)
Dust:0.65” (1.63mbar)
0.8” (2mbar)
3.0” (7.5mbar)
6.0” (15mbar)
0.2” (0.5mbar)
K1
0sec
Off
Imperial
Portrait
Off
EnterPSWsettings
Programmodes
Purgingtime
Minpressure
Alarmpressure
Purgingpressure
Maxpressure
Leakagecomp
K2function
Delayshut-offK1
Bypassoff/on
MetricorImperial
Changepassword
FactoryRestore
LandscapeorPortrait
PowerOFFthenON
PASSWORD/SET
PURGE/PROGRAM
PURGE/ TIME
ENCLOSUR/PRESSP1
ENCLOSUR/PRESSP2
ENCLOSUR/PRESSP3
ENCLOSUR/PRESSP4
LEAKAGE/HYST
PROGRAM/K2
SHUT-OFF/DELAY
BYPASS/N Y
UNITS/MI
CHANGE/PASSWORD
RESTOREDEFAULTS
DISPLAY ROTATION
CYCLEPOWER
Program ApplicationPurgeOperationSpecifics
GasImmediate
Purge
GasDelayed
Purge
GasImmediate
Purge
DustClean
Enclosure
GasDelayed
Purge
Purgestartsonpowerup(SV1)
AfterpurgingEnclosurecontacts(K1)energize
Ifmax.Press(P4)isreached,Sv1turnsoff
EnclosurepowerONduringlossofpressure(K1)
Alarmscanbesetforlowpressure.(K2)
Pressurecompensationturnsonbelow(P2)
Nopurgingisrequiredforprogram5
IncreaseenclosurepressureaboveP1
Menuscreenwillshow’CLEANENCLOSURE’
Cleanenclosure
‘SET’ buttonenergizesenclosure.
PurgestartsaboveP1pressure(SV1)
AfterpurgingEnclosurecontacts(K1)energize
Ifmax.Press(P4)isreached,Sv1turnsoff
EnclosurepowerONduringlossofpressure(K1)
Alarmscanbesetforlowpressure.(K2)
Pressurecompensationturnsonbelow(P2)
PurgestartsaboveP1pressure(SV1)
AfterpurgingEnclosurecontacts(K1)energize
Ifmax.Press(P4)isreached,Sv1turnsoff
EnclosurepowerOFFduringlossofpressure(K1)
Alarmscanbesetforlowpressure.(K2)
Pressurecompensationturnsonbelow(P2)
Purgestartsonpowerup(SV1)
AfterpurgingEnclosurecontacts(K1)energize
Ifmax.Press(P4)isreached,Sv1turnsoff
EnclosurepowerONduringlossofpressure(K1)
Alarmscanbesetforlowpressure.(K2)
Pressurecompensationturnsonbelow(P3)
The7500controllerhas5purgingandpressurizationprogramsavailable.
Belowaretheprograms:
PurgetimeissetinMin:Sec(000:00).Usingthe
incrementsthetime.Holdeitherkeydownforfaster
advance
LEDIndication
PressureP1isthemin. Allowedpressurefor
safeuse.Minvalueis0.3” forgasand0.7”
fordust.P1valuecannotgoaboveP2,P3,P4
PressureP2isusedtoforlowpressurefunction.
Compensationforleakagesforcertainfunctions
willactivateSv1whenbelowP2
PressureP3isusedtoactivatethetime
forpurging.PressureaboveP3indicates
properflowforpurging.Inprogram4P3
willstartcontinuousflowcompensation.
PressureP4isamaximumoverpressure
value.Inreachingthisvaluethedisplay
willread ‘MAX’.IfP4isachievedduring
purgingSV1willshutoffuntilpressure
belowP4.
ENCLOSUR/PRESSP1
ENCLOSUR/PRESSP2
ENCLOSUR/PRESSP3
ENCLOSUR/PRESSP4
Purgetime
Purge1
Purge2
Purge3
Purge4
Purge5
LEDLEDColorDescription
K1
K2
P/SV1
Green
Amber
Blue
Amber
ContactK1isenergized(enclosurecontacts)
ContactK2isenergized(alarmcontacts)
SafepressureP1(minimumencl.press.)
SV1isenergized
ToenterPurgeSetuppressandhold
fingerinpositionfor5seconds