EasyManua.ls Logo

Pfannenberg DTS - Trouble-Shooting

Pfannenberg DTS
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
085 408 164 11
sionsaretobetakenintoaccount).
7)Connectthecoolingunittothepowersource(seesection8.4).
8.4 Power connection
CAUTION:
• Thecoolingunitmustbeconnectedtothemainsbymeansofa
disconnecting device with a contact gap of at least 3 mm when
switched off.
• Notemperaturecontrolmustbeseries-connectedtothecooling
unit feed.
The fuse as indicated on the ID plate must be series-connected
as line protection.
• Powerconnectionandrepairs,ifapplicable,mayonlybecar-
ried out by authorized trained electricians.
Powersupplyconnection(mains):
Both mains voltage and frequency must correspond to the nominal
values indicated on the ID plate of the cooling unit.
• Theinstallationofthepowercableisnotsubjecttoanyspecial
requirements
Attention: The cooling unit may be damaged if the
voltage is too high.
Refers to cooling units for nominal voltages 400 V/440V.
As an option, some units, differenttothestandard (400
V/440V),maybeconnectedtoadifferentmainsvoltage(For
voltagerangeseeenclosedsheet).Thefeedcablesonthe
transformer primary must be unclamped for this.
Attention! The cooling unit may be damaged due to
incorrect direction of rotation.
Before switching on the unit, check the phase sequence of the
three-phase supply in order to prevent damage to the compres-
sor.Directionofrotationmustbetotheright(clockwise).
9 Operating Conditions
• Voltage must be within ± 10 % of the value indicated.
Frequencymustbewithin±3Hzofthevalueindicated.
• Ambient temperature must be below 55 °C (for options see
supplement).
• Usetheunitsuchthatthecoolingcapacitysuitstheactualde-
mand.
• Userefrigerantasindicatedonly.
• Usegenuinesparepartsonly.
10 Putting into operation and function
10.1 General remarks
The cooling unit is provided with an electronic control system. The drawn-
in switch cabinet internal air temperature is measured by a temperature
sensor. By means of a DIP switch on the control board, different
switch cabinet temperatures as well as upper limit temperatures can
beselected(seeaccompanyingsheet).ForunitswithMulti-Controller,
selection is made from a display and control unit. Exceeding the
limit temperature generates an alarm. For units with Comfort- or
Multi-Controller, the lower temperature limit can also be monitored.
Warning!
Ambient conditions and temperature in the switch cabinet must
be in accordance with the values indicated in the supplement.
Warning! Too little heat transfer at the heat exchanger
in the external circuit (condenser).
The cooling unit may only be operated with cover, otherwise
heatdissipationatthecondenserisnotsufcient,andthe
cooling unit may be damaged.
Immediately after the switch-on of the service voltage, the
unit goes into the start-up/test mode. After that the evaporator
fan continues to run. Compressor and condenser fans run
onasrequired(thetemperatureoftheswitchingthreshold
(T
set
)has beenreached, orare switchedoff(temperature
lowerthanswitchingthreshold(T
set
)).
• Freedischargeofanycondensateproducedmustbeprovided
to ensure trouble-free operation.
11 Cleaning and Maintenance
Hazard!
Isolate the cooling unit from the mains before carrying out
any cleaning or maintenance operations.
11.1 Cleaning
The cleaning intervals depend upon the relevant operating conditions.
In particular observe the following instructions.
• Cleantheheatexchangerregularly.
• Cleantheheatexchangerusingasoftbrushorpressurizedair.
• Werecommendthatthecondensaterun-offopeningbechecked
regularly.
Proceed as follows:
1) Disconnectthecoolingunitfromthepowersupply.
2) Removeexternalcover.
3) Cleanheatexchangers
CAUTION:
Protect the electric components against leakage.
CAUTION: Damage to louvres
Do not use any pointed or sharp-edged objects. The ribs
should not be compressed or damaged during the cleaning
process.
CAUTION: Damage to electric connections on the
covering hood
If the covering hood is removed, the electric plug-in connec-
tionsontheinsidemustberemovedbyhand.Duringtting
donotforgettoplug-in!
• Ifthecoolingunitsareprovidedwithafrontltercleanthelter
mat regularly. The cleaning intervals or the intervals for replace-
mentoftheltermatmainlydependuponambientconditions(air
pollution).
• You can rinsetheltermatusingwaterheatedto 40 °C and
commercially available mild detergent. It is possible to remove
any dry dirt by knocking the mat slightly, vacuum cleaning it or
blowing it out.
CAUTION: Damage to the lter mat.
Donotwringtheltermat.Avoidtoosolidawaterjet.
•Iftheltermatisoilyorgreasy,replace.
11.2 Maintenance
The cooling circuit, as a maintenance-free, hermetically sealed closed
system,islledatthefactorywiththenecessarycoolant,checkedfor
leakages and is subjected to a functional check run. The cooling unit
is largely maintenance-free. The components around the external air
circuit require maintenance and cleaning depending upon the ambient
conditions(seeSection11.1).
After each service, the full performance capacity of the condensate
run-off should be checked.

Table of Contents