34 Battery equalization voltage
59.2 Vdc (48 Vdc model Default)
29.6 Vdc (24 Vdc model Default)
Available values: 48.0 ~ 64.0Vdc in
0.1 Vdc increme nts for 48 Vdc
model .
Available values: 24.0 ~ 32.0Vdc in
0.1 Vdc increme nts for 24 Vdc
model .
35
Battery equalization duration
The duration for which the
equalization voltage from
settings menu 34 is held
before the Floating phase is
r eached.
120 min. (Default) Available values: 5 ~ 900 minutes in
5 min. increments.
36
Battery equalization timeout
If the e qualization voltage
from settings menu 34 cannot
be reached within the
duration from s etting s menu
35, once this timeout is
r eached, equalization is ended
and the charger returns to
Floatin
hase.
180 min. (Default) Available values: 5 ~ 900 minutes in
5 min. increments.
37 Equalization interval
30 days (Default) Available values: 0 ~ 90 days in 1-
day increments.
39
Equalization phase: forced
start
Enabled Disabled (Default)
If the battery equalization function is enabled in settings menu 33, this
function can be enabled. If“Enabled”is selectedin this me nu, battery
equalization is immediately force-started and the display main view
will show
(EQ).
If“Disabled”is selected, it will cancel the forced equalizationfunction
until the next scheduled equalization interval as defined in se ttings
menu 37.
will no longer be shown in LCD main page.
40
Reset PV and Load energy
datalogger storage
Not reset (Default) Reset