www.phocos.com 35 | P a g e
If any error occurs, the error
cod e will be displayed for
thre e seconds. After three
seconds, the s creen returns
to the default main view.
Timer Override Setting for AC Output Source Priority
This timer setting is to set up the daily AC output source priority.
Note: If no button is pressed within 1 minute of starting this procedure, the screen will automatically return to t he
default main view.
To define a daily time period in which a specific AC output source priority is to be temporarily activated, follow the
steps below:
1. Press and hold for 3 s econds t o enter the timer set ting for the AC output source priority. The t hree
available priority orders are shown on the display (see chapterDevice Operation Settings Settings
menu 01 for an explanation):
2. From top to bottom the priorities shown in the screen represent:
a. Utility / AC input first (“USB”for Utility Solar Battery)
b. Solar / PV first (“SUB”for Solar Utility Battery)
c. SBU priority (“SBU” for Solar Battery Utility)
3. Press either , or to enter one of the three selectable priorities:
a. = USB
b. = SUB
c. = SBU
4. The selected priority order (USB, SUB or SBU) is shown at the top of the screen. The middle shows t he
starting time and the bottom shows the s topping time in full hours (24h notation). As an example for the
USB priority:
5. Press to select the starting time (middle of screen), it will flash. Now pre ss or to change the
starting time in 1-hour steps.Then, press to confirm the s tarting time, it will stop flashing.
6. Press to select the ending time (bottom of screen), it will flash. Now p ress or to change the
ending time in 1-hour steps. Then, press t o confirm the e nding time, it will stop flashing.
7. Now press to return to main screen.
Timer Override Setting for Battery Charger Source Priority
This timer setting is to set up the daily battery charger source priority.
Note: If no button is pressed within 1 minut e of starting this procedure, the screen it willautomatically return to the
default main view.
Error Code Description
No USB dis k is detected
USB disk is write-protected
File from USB disk has incorrect format or USB stick is incompatible

Other manuals for Phocos Any-Grid Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phocos Any-Grid Series and is the answer not in the manual?

Phocos Any-Grid Series Specifications

General IconGeneral
BrandPhocos
ModelAny-Grid Series
CategoryBattery Charger
LanguageEnglish

Related product manuals