Error codes
8663_en_03 PHOENIX CONTACT 19
0A0D A firmware error occurred. Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
0A18 Invalid Used_Attri-
butes parameter
A reserved bit is set in Used_Attributes. Check the parameters.
0A19 Number of bus devices The end of the frame was exceeded when accessing the
configuration or line 0 was accessed.
Check the access.
0 A1 A Invalid Frame_Refer-
ence (if specified)
The frame reference specified for the service does not
exist.
Check the parameters.
0A1C Number of connected
devices
Maximum number of devices exceeded. Reduce the bus configura-
tion.
0A2F Number of devices is zero. Connect the device and
check the connection.
0A51 A frame reference from 1 to 254 is permitted only. Currently, the value 1 is per-
mitted only.
0A54 The maximum number of I/O points was exceeded. Reduce the number of I/O
points to the maximum num-
ber.
To obtain the exact number,
please refer to the documen-
tation for your controller.
0A60 No configuration frames could be assigned. Create the configuration
frame.
0A70 A reserved bit has been set in the Diag_Info attribute. Check the parameters.
0A73 Device number Device present with a chip version in the local bus that is
not supported.
Replace the device.
0A74 Device number Device of a manufacturer that is not supported present in
the local bus.
Replace the device.
0A75 Device number Device is indicating a serious error (e. g., faulty EE-
PROM).
Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
0A76 Device number The topology used by the device is not supported by the
master.
Replace the device.
0A77 Device number Error at the interface. Check the connection be-
tween the electronics module
and bus base module.
0A7 A Invalid Dev_Type specified during loading. Check the parameters.
0A7B Invalid Dev_ID specified during loading. Check the parameters.
0A7C Invalid Dev_Length specified during loading. Check the parameters.
0A81 Object index Service (e.g, Create_Configuration) could not be exe-
cuted due to PDI communication malfunctions (timeout).
Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
Table 2-1 Error codes for user errors [...]
Code
(hex)
Additional code Meaning Remedy