UM EN AXL F SYS DIAG
20
PHOENIX CONTACT 8663_en_03
0A82 Object index Service (e.g, Create_Configuration) could not be exe-
cuted due to PDI communication malfunctions (num-
ber).
Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
0A83 Object index Service (e.g, Create_Configuration) could not be exe-
cuted due to PDI communication malfunctions (error).
Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
0A90 Device number Device was selected for synchronization, however it
does not support this.
Select a device that supports
synchronization or change
the selection.
0A91 Device number Device was selected for synchronization, however it
does not support the specified cycle time.
Select a different cycle time
or a different device.
0A92 Device number Device was selected for synchronization, but does not
support the specified value for Input_Delay.
Select a different value for In-
put_Delay or a different de-
vice.
0A93 Device number Device was selected for synchronization, but does not
support the specified value for Output_Delay.
Select a different value for
Output_Delay or a different
device.
0A94 Device number Device was selected for synchronization, but does not
support the specified values for Input_Delay and Out-
put_Delay.
Selected different values for
Input_Delay and Output_De-
lay or a different device.
0AFF Call of Reset_Driver during PDI communication. Restart the device. If the
problem still occurs, please
contact Phoenix Contact.
Table 2-1 Error codes for user errors [...]
Code