3. Connection notes
3.1. Mains connection and line protection
CAUTION! Never carry out work on live parts!
Danger to life!
When connecting the 3-phase network, it is essential to observe the terminal identification!
•Protection:
The control supply voltage and control voltage inputs must be operated with power supply modules
in acc. with DIN 19240 (max. 5% residual ripple)!
For devices with 230 V AC control, make sure that the same phase is used for the
control supply voltage as well as the control inputs!
In order to avoid inductive or capacitive decoupling of disturbing pulses where long control wires are
used, we recommend the use of shielded conductors.
If you want to clamp two conductors under one terminal point, you must use a
conductor with the same conductor cross-section.
3.2. Block diagram
25 A (Diazed) - Line protection at a max. conductor cross section of 2.5 mm
2
16 A FF (6.3 x 32 mm) - Device protection
16 A (automatic device B, circuit breaker) - Short circuit (1.5 kA network)
20 A (Motor protection switch) - Short circuit (1.5 kA network)
20 A TRS20R20A (Fuse) - Short circuit ( 5 kA network)
25 A gl-gG (Fuse) - Short circuit (10 kA network)
Fig.2
Reset
Reset
Autoreset
Reset 2
MAN
AUT
RES
Logic
µP
24
VDC
s
U
97
96
95
9796/98
95
& Error
24VDC
L
R
E
230
VAC
s
U
230VAC
L
R
N
E
N
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
ELR W3-230AC/... ELR W3-24DC/...

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact ELR W3 500AC I Series and is the answer not in the manual?

Phoenix Contact ELR W3 500AC I Series Specifications

General IconGeneral
TypeSolid-state relay
Rated Control Supply Voltage24 V DC
Connection MethodScrew connection
Width22.5 mm
Operating frequency50/60 Hz
Protection classIP20
Rated Operating Voltage48 V AC ... 500 V AC
Operating temperature range-25 °C to 60 °C
Storage temperature range-40 °C to +85 °C
Relative humidity95% (non-condensing)
StandardsIEC 60947-4-3
Input voltage24 V DC
Output voltage48 V AC ... 500 V AC
Output current0.15 A ... 50 A (See derating curve)
Input voltage range19.2 - 30 V DC
Input frequency range47 - 63 Hz
Switching ModeZero voltage switch

Related product manuals