Overview
Operating Manual PNOZ m B0
1002660-EN-02
7
Overview
Range
} Base unit BA PNOZ m B0
} Terminator
} Documentation on data medium
Unit features
Using the product BA PNOZ m B0:
Base unit of the configurable control system
The product has the following features:
} Can be configured in the PNOZmulti Configurator
} Semiconductor outputs:
4 safety outputs
Depending on the application, up to PL e of EN ISO 13849-1 and up to SIL CL 3 of EN
IEC 62061
} 12 inputs for connecting, for example:
Emergency stop pushbuttons
Two-hand pushbuttons
Safety gate limit switches
Reset buttons
Light beam devices
– Scanners
Enabling switches
– PSEN
Operating mode selector switches
} 8 configurable inputs/outputs
Can be configured as:
Inputs (see above for connection options)
or
Auxiliary outputs
} 4 configurable outputs
Can be configured as:
Auxiliary outputs
or
Test pulse outputs
} LED for:
Error messages
– Diagnostics