Technical details
Operating Manual PNOZ ms2p HTL
1001401-EN-04
31
Mechanical data
Conductor cross section with spring-loaded terminals
1 core flexible without crimp connector 0,25 - 1,50 mm², 24 - 16 AWG
1 core flexible with crimp connector 0,25 - 0,75 mm², 24 - 20 AWG
Spring-loaded terminals: Terminal points per connec-
tion
1
Stripping length with spring-loaded terminals 9 mm
Dimensions
Height 94,0 mm
Width 45,0 mm
Depth 121,0 mm
Weight 220 g
Where standards are undated, the 2009-06 latest editions shall apply.
8.1 Safety characteristic data
Operating
mode
EN ISO
13849-1:
2015
PL
EN ISO
13849-1:
2015
Category
EN IEC
62061
SIL CL
EN IEC
62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
13849-1:
2015
T
M
[year]
Initiator PL e Cat. 3 SIL CL 3 3,68E-09 SIL 3 4,84E-05 20
Incremental
encoder
PL e Cat. 3 SIL CL 3 6,73E-09 SIL 3 8,18E-05 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.