Relay outputs 774700 774701 774703
Utilisation category of
safety contacts
AC1 at 400 V 400 V 400 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 5 A 5 A 5 A
Max. power 2000 VA 2000 VA 2000 VA
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 2000 VA 2000 VA 2000 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 200 W 200 W 200 W
Utilisation category of
auxiliary contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 2000 VA 2000 VA 2000 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 200 W 200 W 200 W
Utilisation category
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 5 A 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 7 A 7 A 7 A
Utilisation category of
auxiliary contacts
AC15 at 230 V 230 V 230 V
Max. current 5 A 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 7 A 7 A 7 A
Utilisation category in ac-
cordance with UL
Voltage 240 V AC G. P. 240 V AC G. P. 240 V AC G. P.
With current 8 A 8 A 8 A
Voltage 24 V DC Resistive 24 V DC Resistive 24 V DC Resistive
With current 5 A 5 A 5 A
Pilot Duty B300, R300 B300, R300 B300, R300