Conventional thermal
current while loading
several contacts
787520 787522 787530
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact – – 8 A
Conv. therm. current
with 2 contacts – – 7,8 A
Conv. therm. current
with 3 contacts – – 6,5 A
Conv. therm. current
with 4 contacts – – 5,5 A
Conv. therm. current
with 5 contacts – – 5 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 7,8 A 7,8 A 7,8 A
Conv. therm. current
with 3 contacts 6,5 A 6,5 A 6,5 A
Conv. therm. current
with 4 contacts 5,5 A 5,5 A 5,5 A
Conv. therm. current
with 5 contacts 5 A 5 A 5 A
Times 787520 787522 787530
Switch-on delay
With automatic start
typ. 400 ms 400 ms 400 ms
With automatic start
max. 850 ms 850 ms 550 ms
With automatic start
after power on typ. 400 ms 400 ms 750 ms
With automatic start
after power on max. 870 ms 870 ms 1.050 ms
With monitored start
typ. 40 ms 40 ms 35 ms
With monitored start
max. 70 ms 70 ms 60 ms