Connecting the Control System PNOZmulti
Installation Manual PNOZmulti Installation Manual
1002265-EN-02
36
5.13.6 Wiring
Please observe the following when wiring:
} Cable runs between the connected units:
PNOZmulti - PNOZmulti: Max. 100m
PNOZelog - PNOZmulti cascaded directly: Max. 10m
Cable material: see Technical details
} Outside the control cabinet, both the wires from the cascading input (CI+, CI-) and the
wires from the cascading output (CO+, CO-) must be laid in separate multicore cables.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pilz PNOZmulti and is the answer not in the manual?

Pilz PNOZmulti Specifications

General IconGeneral
PLPL e
Expansion ModulesYes, via base units and extension modules
ProgrammingPNOZmulti Configurator (graphical configuration software)
Safety standardsEN ISO 13849-1, EN 62061, IEC 61508
SILSIL 3
Operating voltage24V DC (typically, but can vary depending on the specific module)
Safety categoryCategory 4