22 - ATR144 - User manual
digital input active, otherwise the regulation is of heating
type;
• A.i . 0: Zero tare function: brings the related analogue input
to 0.
• M. reS.: Allows the reset of the command and alarm outputs
if manual reset is active.
• t .1 . r u n : If timer 1 is enabled (par. 186 t m r .1 different from
di s a b .), with digital input active, the timer is switched to
RUN, otherwise is kept in STOP;
• t .1 . s . e . : If timer 1 is enabled (par. 186 t m r.1 different from
di s a b .), acting on the digital input, the status of the timer
switches from STOP to RUN e vice versa;
• t .1 . s t a . : If il timer 1 is enabled (par. 186 t m r.1 different from
di s a b .), acting on the digital input, the timer is switched to
RUN;
• t .1 . e n d . : If il timer 1 is enabled (par. 186 t m r .1 different from
di s a b .), acting on the digital input, the timer is switched to
STOP;
• t .2. ru n: If timer 2 is enabled (par. 189 t m r. 2 different from
di s a b .), with digital input active, the timer is switched to
RUN, otherwise is kept in STOP;
• t .2. s . e.: If timer 2 is enabled (par. 189 t m r. 2 different from
di s a b .), acting on the digital input, the status of the timer
switches from STOP to RUN e vice versa;
• t .2. s ta .: If timer 2 is enabled (par. 189 t m r. 2 different from
di s a b .), acting on the digital input, the timer is switched to
RUN;
• t .2. e n d .: If timer 2 is enabled (par. 189 t m r. 2 different from
di s a b .), acting on the digital input, the timer is switched to
STOP;
• Lo . cfG.: With digital input active, the access to setpoint
configuration/modification is locked;
• u p.key: simulates the operation of the up button.
• down.k.: simulates the operation of the down button.
• fn c . k.: simulates the operation of the FNC button.
• s et . k.: simulates the operation of the SET button.