8 - ATR144 - User manual 
4.2  Hardware features
Analogue 
input
AI1:
Configurable via software.
Input: Thermocouple
type K, S, R, J,T,E,N,B.
Automatic compensation 
of cold junction from 
-25…85° C.
Thermoresistances: PT100, 
PT500, PT1000, Ni100, 
Ni120, PTC 1K, NTC 10K (β 
3435K and β3694K), NTC 
2252 (β3976K)
Input V/mA: 0-1 V, 0-5 V, 
0-10 V, 0-20 o 4-20 mA, 
0-60 mV.
Pot. Input: 1...150 KΩ.
Tolerance (25° C)
± 0.2% ± 1 digit 
(on F.s.) for 
thermocouple, 
thermoresistance 
and V/mA.
Cold junction 
accuracy 0.1° C/°C.
Impedence:
0-10 V: Ri>110 KΩ
0-20 mA: Ri<5 Ω
0-40 mV: Ri>1 MΩ
Relay 
outputs
Configurable as command
and alarm output.
Contacts:
5 A - 250 VAC 
Resistive load.
SSR 
outputs
Configurable as command
and alarm output.
12 V, 25 mA.
Power-
supply
Extended power-supply 
24..230 VAC/VDC ±15% 
50/60 Hz
Consumption: 5 
Watt/VA