8.7 Automatic / Manual regulation for %
output control
This function allows to switch from automatic functioning to
manual command of the output percentage. The cycle time is
set in parameter 45 c. t. 1 (“Cycle Time 1”).
With par. 29 A. m a.1. it is possible to select two modes.
1 First selection (enab.) allows to eneble with FNC the
writing p.--- on display 1, while on display 2 is showed
autom.
Press SET to visualize manu.; it’s now possible, during the
process visualization, modify through the keys
and
the output percentage. To back to automatic, with the
same procedure, select autom. on display 2: immediately
led M switches off and functioning backs to automatic.
2 Second selection (en.sto.) enables the same functioning
but with two important variants:
If there is a temporary power failure or after switch-off,
the manual functioning as well as the previous output
percentage value will be maintained at restarting.
If the sensor breaks during automatic functioning, the
controller switches to manual mode while maintaining the
output percentage command unchanged as generated by
the PID immediately before breakage.
Ex: on an extruder the command in percentage of the
resistance (load) is maintained also in case of input sensor
failure.