30 - ATR144 - User manual
8.12 Pre-programmed cycle
Pre-programmed cycle function activates by setting
En a b.
on
parameter 109 p r. cY. .
Controller reaches setpoint 1 basing on the gradient set on
par am ete r 111 SS. G r. , then it reaches max. power up to setpoint
2. When the process reaches max. power, this setpoint is
maintained for the time set on parameter 115 ma.t.i..
At expiry, process will reach ambient temperature according
to gradient entered on parameter 116 fa . G r. , then command
output will be disabled and display will visualize Sto p.
Setpoint 1
Setpoint 2
Maintenance time
Mantenimento
Cooling
RareddamentoMax Power
Max Potenza
Rising gradient
Gradiente di salita
Cycle starts at each activation of the controller, or via digital
input if it is enabled for this type of functioning (parameters
94 d.i.1.F., or 101 d .i .2.F. set as
st./st.
or
rUn
).