EasyManua.ls Logo

Pixsys ATR144 - Table of configuration parameters; GROUP A - R. in.1 - Analogue input 1

Pixsys ATR144
93 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46 - ATR144 - User manual
12 Table of Configuration Parameters
12.a
GROUP A -
A . i n .1
- Analogue input 1
1
S E N .1
Sensor AI1
Analogue input configuration / sensor AI1 selection
tc. k
Tc-K -260° C..1360° C. (Default)
tc. s
Tc-S -40° C..1760° C
tc. r
Tc-R -40° C..1760° C
tc. J
Tc-J -200° C..1200° C
Tc. T
Tc-T -260° C..400° C
tc. E
Tc-E -260° C..980° C
tc. N
Tc-N -260° C..1280° C
tc. b
Tc-B 100° C..1820° C
Pt10 0
Pt100 -200° C..600° C
ni10 0
Ni100 -60° C..180° C
ni12 0
Ni120 -60° C..240° C
ntc 1
NTC 10K β3435K -40° C..125° C
ntc 2
NTC 10K Omega -40° C..150° C
ntc 3
NTC 2252 Omega -40° C..150° C
Ptc
PTC 1K -50° C..150° C
Pt500
Pt500 -200° C..600° C
Pt1k
Pt1000 -200° C..600° C
rsvd.1
Reserved
rsvd.2
Reserved
0-1
0..1 V
0-5
0..5 V
0-10
0..10 V
0-20
0..20 mA
4-20
4..20 mA
0-60
0..60 mV
Po t.
Potentiometer (set the value on parameter 6)