46 - ATR144 - User manual
12 Table of Configuration Parameters
12.a
GROUP A -
A . i n .1
- Analogue input 1
1
S E N .1
Sensor AI1
Analogue input configuration / sensor AI1 selection
tc. k
Tc-K -260° C..1360° C. (Default)
tc. s
Tc-S -40° C..1760° C
tc. r
Tc-R -40° C..1760° C
tc. J
Tc-J -200° C..1200° C
Tc. T
Tc-T -260° C..400° C
tc. E
Tc-E -260° C..980° C
tc. N
Tc-N -260° C..1280° C
tc. b
Tc-B 100° C..1820° C
Pt10 0
Pt100 -200° C..600° C
ni10 0
Ni100 -60° C..180° C
ni12 0
Ni120 -60° C..240° C
ntc 1
NTC 10K β3435K -40° C..125° C
ntc 2
NTC 10K Omega -40° C..150° C
ntc 3
NTC 2252 Omega -40° C..150° C
Ptc
PTC 1K -50° C..150° C
Pt500
Pt500 -200° C..600° C
Pt1k
Pt1000 -200° C..600° C
rsvd.1
Reserved
rsvd.2
Reserved
0-1
0..1 V
0-5
0..5 V
0-10
0..10 V
0-20
0..20 mA
4-20
4..20 mA
0-60
0..60 mV
Po t.
Potentiometer (set the value on parameter 6)