User manual - ATR144- 33
Modbus
address
Description
Read
Write
Reset
value
723
Last character of the custom alarm
message 1
RW 0
751
First character of the custom alarm
message 2
RW “u“
... RW -
773
Last character of the custom alarm
message 2
RW 0
1000 AI1 value (degrees with tenth) RO -
1001 Real setpoint (gradient) RO 0
1002
Alarms status (0=absent, 1=present)
Bit0 = Alarm 1
Bit1 = Alarm 2
RO 0
1003
Error flags 1
Bit0 = AI1 process error (sensor 1)
Bit1 = Cold junction error
Bit2 = Safety error
Bit3 = Generic error
Bit4 = Hardware error
Bit5 = Errore L.B.
Bit6 = Parameters out of range error
Bit7= CPU eeprom writing error
Bit8= RFid eeprom writing error
Bit9= CPU eeprom reading error
Bit10= RFid eeprom reading error
Bit11= Eeprom calibrations bench
corrupted
Bit12= Eeprom constants bench
corrupted
Bit13 = Missing calibrations error
Bit14 = Eeprom CPU bench
parameters corrupted
Bit15 = Eeprom CPU setpoint bench
corrupted
RO 0