36 - ATR144 - User manual
Modbus
address
Description
Read
Write
Reset
value
1210
Tune management
With automatic Tune (par. 36 t u n .1
= Auto):
0=autotunig function OFF
1=autotuning ON
RO 0
With manual Tune (par. 36 t u n .1 =
manu. o On cE):
0=autotunig function OFF
1=autotuning ON
R/W 0
With synchronized Tune (par. 36
t u n .1 = SYn cH.):
0=autotunig function OFF
1=command output OFF (forces the
cooling)
2=command output ON (forces the
heating)
3=autotuning ON
4=autotuning ended
R/W 0
1211
Automatic/manual selection
0=automatic; 1=manual
R/W 0
1212
Command output percentage
(0-10000)
Heating output percentage with
regulation in double loop (0-10000)
R/W 0
1213
Command output percentage
(0-1000)
Heating output percentage with
regulation in double loop (0-1000)
R/W 0
1214
Command output percentage
(0-100)
Heating output percentage with
regulation in double loop (0-100)
R/W 0