38 - ATR144 - User manual
Modbus
address
Description
Read
Write
Reset
value
1304
Alarm 1 setpoint, with decimal
point selection
Alarm 1 lower setpoint if Par. 62
AL.1.F. = A.band
R/W EEPROM
1305
Alarm 1 lower setpoint if Par. 62
AL.1.F. = A.band, with decimal point
selection
R/W EEPROM
1306
Alarm 2 setpoint, with decimal
point selection
Alarm 2 lower setpoint if Par. 78
AL.2.F. = A.band
R/W EEPROM
1307
Alarm 2 lower setpoint if Par. 78
AL.2.F. = A.band, with decimal point
selection
R/W EEPROM
1400
Remote process reset: by writing 1,
the ATR144 uses for the process the
value measured by the analogue
input instead of the one written in
the word 1401
W -
1401
Remote process. The number
written in this word will be the
process value that the device
uses for setting and alarms (ADC
disabled)
W -
2001 Parameter 1 R/W EEPROM
2002 Parameter 2 R/W EEPROM
... Parameter ... R/W EEPROM
2223 Parameter 223 R/W EEPROM